OUTPUT VALUES
| Standby Power | Voltage | 231/400 |
| Standby Power | kVA | 150 |
| Standby Power | kW | 120 |
| Standby Power | Amper | 217 |
| Prime Power | Voltage | 231/400 |
| Prime Power | kVA | 135 |
| Prime Power | kW | 108 |
| Prime Power | Amper | 195 |
DIMENSIONS & WEIGHT
| Without Canopy | Width | 1100 mm |
| Without Canopy | Length | 2500 mm |
| Without Canopy | High | 1700 mm |
| Without Canopy | Weight | 1500 kg |
| Without Canopy | Fuel Tank Capacity | 280 lt |
| With Canopy | Width | 1100 mm |
| With Canopy | Length | 3100 mm |
| With Canopy | High | 1850 mm |
| With Canopy | Weight | 1900 kg |
| With Canopy | Fuel Tank Capacity | 280 lt |
ALTERNATOR INFORMATIONS
| Standby Power (kVa/kw) | 150/120 |
| Prime Power (kVa/kw) | 135/108 |
| Brand | Leroy Somer |
| Output Voltage (V) | 231/400 |
| Frequency (Hz) | 50 |
| Stationary Vol. Regulation(±) | 0,01 |
| Short Circuit Current | %300 (10 sec) |
| Insulation | H |
| Protection | IP23 |
| E ciency (%) | 93,2 |
| Overloading | 110% for 1 hour |
| Power Factor (cos Q=0.8) | 0,8 |
| Tot. Harmonic Dist. Rate | <2 % |
| Connection Type | Star |
| Number of Pole | 4 |
| Number of Bearing | Single |
DIESEL ENGINE
| Brand | Perkins |
| Model | 1106A-70TG1 |
| Max. Total Output Pow. (kWm/hp) | 133,5 / 179 |
| Cylinder Displacement (lt) | 5,99 |
| Cylinder Orientation | 6 Single Line |
| Bore x Stroke(mm*mm) | 100*127 |
| Compression Ratio | 17;1 |
| Governor Type | Electronic |
| Rotation | 1500 RPM |
| Aspiration System | Turbo AAC |
| Injection | Direct |
| Cooling System | Water Cooled |
| Electrical System(V DC) | 12 |
| Oil Capacity (lt) | 19 |
| Engine Coolant Capacity (lt) | 37,2 |
| Fuel Cons. %50 (lt/h) | 16,5 |
| Fuel Cons. %75 (lt/h) | 24,1 |
| Fuel Cons. %100 (lt/h) | 31,5 |