Products Detail

  • Brand: Volvo
  • Model:TAD532GE
  • Alternator Brand: Leroy Somer
  • Standby Power (kVa/kw): 145/116

OUTPUT VALUES

Standby Power Voltage 230/400
Standby Power kVA 145
Standby Power kW 116
Standby Power Amper 209
Prime Power Voltage 230/400
Prime Power kVA 132
Prime Power kW 105
Prime Power Amper 190

DIMENSIONS & WEIGHT

Without Canopy Width 1100 mm
Without Canopy Length 2500 mm
Without Canopy High 1650 mm
Without Canopy Weight 1270 kg
Without Canopy Fuel Tank Capacity 250 lt
With Canopy Width 1100 mm
With Canopy Length 3100 mm
With Canopy High 1900 mm
With Canopy Weight 1600 kg
With Canopy Fuel Tank Capacity 250 lt

ALTERNATOR INFORMATIONS

Standby Power (kVa/kw) 145/116
Prime Power (kVa/kw) 132/105
Brand Leroy Somer
Output Voltage (V) 230/400
Frequency (Hz) 50
Stationary Vol. Regulation(±) 0,01
Short Circuit Current %300 (10 sec)
Insulation H
Protection IP23
E ciency (%) 88
Overloading 110% for 1 hour
Power Factor (cos Q=0.8) 0,8
Tot. Harmonic Dist. Rate <1 %
Connection Type Star
Number of Pole 4
Number of Bearing Single

DIESEL ENGINE

Brand Volvo
Model TAD532GE
Max. Total Output Pow. (kWm/hp) 125/170
Cylinder Displacement (lt) 4.76
Cylinder Orientation 4 Single Line
Bore x Stroke(mm*mm) 108 x 130
Compression Ratio 17.1
Governor Type Electronic
Rotation 1500 RPM
Aspiration System Natural
Injection Direct
Cooling System Water Cooled
Electrical System(V DC) 12
Oil Capacity (lt) 13
Engine Coolant Capacity (lt) 19.7
Fuel Cons. %50 (lt/h) 15
Fuel Cons. %75 (lt/h) 23
Fuel Cons. %100 (lt/h) 31